Standards - Scenario 2

Image
This post is inspired by the 2017 Philippine Electrical Code (PEC) Appendix D Example D12 (Voltage Regulators, Three-Phase). SITUATION A three-phase automatic voltage regulator (AVR) rated 30 kVA, 60 Hertz, 350-530 Volts input, 230 Volts output needs a feeder circuit from the main service panel. The AVR is installed in an air-conditioned data center with raised floors, and the conduit for electric conductors shall be run underneath. The wires to be used are made of copper conductors, with insulation rated for 75 degC operating temperature and of type THW (Thermoplastic, Heat-resistant, for Wet location). The raceway for the circuit is a rigid PVC Schedule 80 conduit. What size of 3ph circuit breaker, wires, and raceway are needed? ANALYSIS 1.) ONE-LINE DIAGRAM              i,avr,1L ---> o|---V,msp,LN---V,avr,LN---|> 2.) CIRCUIT CALCULATIONS 2.1.) Kirchhoff's Voltage Law, LN: -V,msp,LN + V,avr,LN = 0 V,avr,LN = V,msp,LN 2...

Standards - Scenario 1

Image
This post is inspired by the 2017 Philippine Electrical Code (PEC) Appendix D Example D11 (Voltage Regulators, Single-Phase). SITUATION A single-phase automatic voltage regulator (AVR) rated 5 kVA, 60 Hertz, 165-280 Volts input, 230 Volts output needs a feeder circuit from the main service panel. The AVR is installed in an air-conditioned data center with raised floors, and the conduit for electric conductors shall be run underneath. The wires to be used are made of copper conductors, with insulation rated for 75 degC operating temperature and of type THW (Thermoplastic, Heat-resistant, for Wet location). The raceway for the circuit is a rigid PVC Schedule 80 conduit. What size of 1ph circuit breaker, wires, and raceway are needed? ANALYSIS 1.) ONE-LINE DIAGRAM i,avr,1ph ---> o|---V,msp,1ph---V,avr,1ph---|> 2.) CIRCUIT CALCULATIONS 2.1.) Kirchhoff's Voltage Law, 1ph: -V,msp,1ph + V,avr,1ph = 0 V,avr,1ph = V,msp,1ph 2.2.) Power equation, ...

Standards - Note 4

Image
RACEWAY SIZES (CONDUIT AND TUBING) 1.) Raceway Sizing There are three options for sizing raceways according to 2017 PEC Table 10.1.1.1 [ or 2017 NEC Chapter 9 Table 1 ], based on cross-sectional areas: A.) 53% raceway area for 1 conductor (a multiconductor cable is treated as a single conductor [Note 9]) B.) 31% raceway area for 2 conductors C.) 40% raceway area for over 2 conductors 1.1.) Choosing Between Alternatives For future expansion purposes, option (A) is far from practical. This may have use in very specific installations that are assumed to be not needing any expansions, but upgrades will definitely happen and option (A) will eventually become a bottleneck. Option (B) for 2 conductors having a smaller area than either option (A) for 1 conductor or option (C) for over 2 conductors may seem nonsensical, but it actually does make sense. Having 2 conductors usually means 2 live wires supplying loads that may require an equipment grounding conductor ...

Standards - Note 3

Image
WIRE AMPACITIES, INSULATORS, AND IMPEDANCES Below are some useful tables pertaining to ampacities, insulators, and impedances of various wires. These are derived from the 2017 Philippine Electrical Code [ or the 2017 National Electrical Code ], but are rearranged in a manner that is easier to interpret and understand. 1.) Allowable Ampacities of Insulated Conductors in Raceway. The areas, ampacities, and insulation types of the following tables are based on 2017 PEC Table 3.10.2.6(B)(16) [ or 2017 NEC Table 310.15(B)(16) ]. 1.1.) Copper Wire Ampacities --------------------------------------- |  Copper  |  Insulation Max Op. Temp | --------------------------------------- |   Area   | 60degC | 75degC | 90degC | |   mm^2   |  Amps  |  Amps  |  Amps  | --------------------------------------- |    2.0   |    15  |    20  |    25  ...